Member Details
- Product Details
- Company Profile
RCCB
■ Provides protection against earth fault/leakage current and function of isolation
High breaking current withstand capacity
■ Applicable to terminal and pin/fork type busbar connection
■ Fire resistant plastic parts endures abnormal heating and strong impact
■ Automatically disconnect the circuit when earth fault/leakage current occurs
and exceeds the rated sensitivity
■ Independent of power supply and line voltage, and free from external
interference, voltage fluctuation
Technical Data
Mode | Electro-magnetic type, electronic type |
Residual current characteristics | A, AC |
Pole No. | 2, 4 |
Rated making and breaking capacity | 630A |
Rated current(A) | 25, 40, 63 |
Rated voltage | 240/415V AC |
Rated frequency | 50/60Hz |
Rated residual operating current IΔn(mA) | 10, 30, 100, 300, 500 |
Rated residual non operating current IΔno | 0.5IΔn |
Rated conditional breaking current Inc | 3000A |
Rated conditional residual breaking current IΔc | 3000A |
Tripping duration | Instantaneous tripping≤0.1s |
Residual tripping current range | 0.5IΔn~IΔn |
Electro-mechanical endurance | 4000 cycles |
Connection capacity | Rigid conductor up to 25mm2 |
Connection terminal | Screw terminal |
Pillar terminal with clamp | |
Fastening torque | 2.0 Nm |
Installation | On symmetrical DIN rail 35mm |
Panel mounting |