Miniature Circuit Breaker
Member Details
- Product Details
- Company Profile
Miniature Circuit Breaker
Poles description
1P/2P/3P/4P
Device Application
Distribution
Poles
1P/2P/3P/4P
Number of Protected Poles
1/2/3/4
[In] Rated Current
1A/2A/4A/6A/10A/16A/20A/25A/32A/40A/50A/63A
Network Type
AC
Trip Unit Technology
Thermal-magnetic
curve code
B/C/D
Breaking Capacity
4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Suitability for Isolation
Yes conforming to IEC 60898-1
Network Frequency
50/60 Hz
[Ue] Rated Operational Voltage
230 V AC 50/60 Hz
Magnetic Tripping Limit
5...10 x In
[Ics] Rated Service Breaking Capacity
4.5 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
[Ui] Rated Insulation Voltage
500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] Rated Impulse Withstand Voltage
4 kV conforming to IEC 60898-1
Contact Position Sndicator
Yes
Control Type
Toggle
Local Signalling
Without
Mounting Mode
Clip-on
Mounting Support
DIN rail
9 mm pitches
2/4/6/8
Mechanical Durability
10000 cycles
Electrical Durability
4000 cycles
Connections - Terminals
Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tightening Torque
3.5 N.m top or bottom
Earth-Leakage Protection
Without