CQB91LE-40 6kA Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)
CQB91LE-40 6kA Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)

CQB91LE-40 6kA Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)

Member Details

Zhejiang Chuangqi Electric Co., Ltd.

Wenzhou,Zhejiang,China

Manufacturer

  • Product Details
  • Company Profile

CQB91LE-40 residual current operated circuit breaker is suitable for AC 50Hz, rated voltage single pole two lines 230V, rated current to 40A line. When the person is electric shocked or the leakage current of the power grid exceeds the specified value, the residual current operated circuit breaker can quickly cut off the faulty power supply in a very short time to protect the safety of the human body and the electrical equipment. The residual current operated circuit breaker has overload and short circuit protection functions, which can be used to protect the line or motor from overload and short circuit, and can also be used as an infrequent conversion start of the line under normal conditions.


1  Application

CQB91LE-40 residual current operated circuit breaker is suitable for AC 50Hz, rated voltage single pole two lines 230V, rated current to 40A line. When the person is electric shocked or the leakage current of the power grid exceeds the specified value, the residual current operated circuit breaker can quickly cut off the faulty power supply in a very short time to protect the safety of the human body and the electrical equipment. The residual current operated circuit breaker has overload and short circuit protection functions, which can be used to protect the line or motor from overload and short circuit, and can also be used as an infrequent conversion start of the line under normal conditions.

 The product complies with GB/T16917.1 and IEC61009-1 standards.

 

2  Type designation

4  Technical data

Specifications                         

Rated voltage(V)

AC230V

Rated current(A)

6A,10A,16A,20A,25A,32A,40A

Leakage characteristics                       

A,  Ac

Rated tripping current lrn

10mA,30mA,100mA

Pole

1P+N

Rated breaking capacity lcs(A)

B、C:4.5/6kA 

Tripping time

0.1s

Rated residual making& breaking capacity 

500A

Tripping Curves

B、C

Mechanical & Electrical life

Mechanical≥6000;Electrical:≥4000

Connecting wire (mm2)

2mm²:6A~16、2.5mm²:20~25、4mm²:32~40

Pollution degree

2

Protection class

IP20

Overvoltage category

Ⅱ、Ⅲ

  Table 2   Tripping time

Type 

ln (A)

lrn (mA)

Operating time:(s)

lrn

2lrn

5lrn

General type

Any value

Any value

0.1

0.05

0.04

 

  Table 3  Tripping characteristics (Reference temperature 30℃)

Item 

Type 

Test current

Status 

Time limit for tripping or non-tripping

Expected result

Remarks

a

B、C、

1.13ln

Cold 

t≤1h

Non-tripping

Current smoothly rises to specified value within 5s

b

B、C、

1.45ln

Following item a test

t≤1h

Tripping

c

B、C、

2.55ln

Cold

1s<t<60s(ln≤32A)

1s<t<120s(ln>32A)

Tripping

d

B

C

3ln

5ln

Cold

t≤0.1s

Non-tripping

Switch on the power supply by closing the auxiliary switch

e

B

C

5ln

10ln

Cold

t≤0.1s

Tripping

Switch on the power supply by closing the auxiliary switch

Note: The term "cold " means that the test is carried out at a reference calibration temperature without load before the test. 


 

5 Conductor requirements and cross-sectional area

Nominal cross-sectional area(mm2

Rated current (A)

1

In≤6

1.5

<p style=margin:0cm;margin-bottom:.0001p